Tellhow (Shenzhen) Electric Technologies Co., Ltd.
Chinese professional electrical equipments manufacturer

TZN1-12 Vacuum Circuit Breaker

By admin • Oct 10th, 2008 • Category: Vacuum Circuit Breakers SF6 Load Break Switches
1. General
TZN1-12 series of indoor MV vacuum circuit breakers are used in the indoor switchgear rated 12 kV, 50(60)Hz. They are suitable for making different types of loads and frequent operation, to protect and control the electric equipments in industrial & mining enterprises, power plants and substations.

The main electric conduction loop of the circuit breaker (TZN1-12 series) is casted with epoxy resin by APG technics, embedding its vacuum arc extinguish chamber and main loop as an integration. Thereby, its insulation performs with high strength, the size is small, and the surface of its vacuum arc extinguishing chamber avoids the influence of ambient environment, realizing the maintenance-free purpose. Main features:

  • small size,
  • water-condensation proof,
  • high insulation,
  • pollution-proof,
  • low resistance,
  • free maintenance.
2. Normal Service Condition
  • Ambient temperature: -15 ℃ ~ +40 ℃
  • Altitude: ≤1000m
  • Relative humidity: daily average relative humidity ≤ 95%; monthly average relative humidity ≤ 90%
  • Free from fire, explosion, heavy pollution, chemical corrosion and severe vibration.
  • Earthquake intensity ≤ 8 degree
  • If the service condition differs from the above , the user should consult it with manufacturer.
3. Technical Parameters
No. Item Unit Parameter
1 Rated voltage kV 12
2 Rated frequency Hz 50(60)
3 Rated short-time power frequency withstand voltage(1 min) kV 42
4 Rated lightning impulse withstand voltage kV 75
5 Rated current A 630
1250
630
1250
1250
1600
2000
1250、1600
2000、2500
3150
6 Rated short-time withstand
current
kA 20 25 31.5 40
7 Rated peak withstand current kA 50 63 80 100
8 Rated short-circuit breaking
current
kA 20 25 31.5 40
9 Rated short-circuit making
current
kA 50 63 80 100
10 Rated operating sequence / O-0.3s-CO-180s-CO
O-180s-CO-180s-CO(40kA)
11 Short-circuit current breaking
times
times 274
12 Rated capacitor bank breaking
current
A 630/400
13 Mechanical
endurance
times 10000
4. Dimensions (withdrawable type)
5. Typical Electric Diagram (withdrawable type)

Related posts:

  1. TZN1-12/M Vacuum Circuit Breaker 1. General   TZN1-12/M series of indoor permanent-magnetic vacuum...
  2. TZN3-24 Vacuum Circuit Breaker 1. General TZN3-24 series of indoor HV vacuum circuit...
  3. TZN2-12 Vacuum Circuit Breaker 1. General TZN2-12 series of indoor vacuum circuit breakers...
  4. TZN2C-12 Vacuum Circuit Breaker 1. General TZN2C-12 series of indoor laterally vacuum circuit...
  5. TZN4-40.5(36) Vacuum Circuit Breaker 1. General TZN4-40.5(36) series indoor HV AC vacuum circuit...

Related posts brought to you by Yet Another Related Posts Plugin.

admin is
Email this author | All posts by admin

INQUIRY