XBZ-12 Pre-installed Substation
By admin • Oct 11th, 2008 • Category: Terminal Distribution Equipments
| 1. General |
| |
|
This products is a new-generation semi-embedded pre-fabricated substation, that is to say, part of the substation is embedded under the ground. It has completely realized the following features: integration of high-voltage primary and secondary system; modular assembling structure; making the construction work as factory, and easy construction. The product is suitable to be used in the streets of the downtown area and the residential quarters, it can greatly save the installing areas Furthermore, it can solve the problem of area occupying and sheltering from vision. It is lower and smaller.
Product features:
- Low height, not block sight.
- Compact structure, small size, low price.
- Good appearance, high assembly capability.;
- Short construction period, low investment.
- Convenient for installation.
- Safe and reliable
- High mechanical bending-resistance ability, high impact-resistance, insolation -resistance ,
- radiation-proof, high heat isolation.
- Design humanization
|
 |
| |
| 2. Normal Service Condition |
| |
- Ambient temperature: -15 ℃ ~ + 40 ℃
- Altitude: ≤ 2000m
- Relative humidity: daily average relative humidity ≤ 95%; monthly average relative humidity ≤ 90%
- Free from fire, explosion, heavy pollution, chemical corrosion and severe vibration.
- The earthquake intensity ≤ 8 degree
- The degrees of inclination of installation ≤3 degrees
- If the service condition differs from the above , the user should consult it with manufacturer.
|
| |
| 3. Configuration |
| |
| Apparatus |
Type |
Manufacturer |
| HV switchgear |
Gas-insulated switchgear |
RAG-FR\FFR |
R&A |
| RM6-IQ\IQI |
Schneider |
| SafeRing-CF/CCF |
ABB |
| RMU |
XGN15-12 |
TELLHOW |
| Transformer |
Day transformer |
SC(G)B-10 |
ABB/CEEG |
| Oil transformer |
S9-M |
HAINAN WEITE |
| LV switchgear |
/ |
MNS |
ABB |
| / |
SIVACON -8PT |
SIEMENS |
| / |
GGD |
TELLHOW |
| enclosure |
Metal material |
/ |
TELLHOW |
| Nonmetal material |
/ |
WEITELIE |
|
| |
| 4. Structure |
| |
 |
| |
| 5. Technical Parameters |
| |
| Item |
Unit |
HV units |
Transformer |
LV units |
| Rated voltage |
kV |
12 |
10/0.4 |
0.4 |
| Rated isolation level |
1min power frequency withstand voltage |
42 |
35 |
2.5 |
| Lightning impulse withstand voltage( full wave) |
75 |
|
|
| Main busbar |
Rated current |
A |
630 |
28.8/721 |
100~1200 |
| Rated short time withstand current |
kA |
20/3S |
|
15~65/3S |
| Rated peak withstand current |
50 |
|
65 |
| Dimension(depth*width*height) |
Single
(circuit) |
mm |
2300×2000×1640 |
| Protection class |
Enclosure
IP4X |
| Rated capacity |
500kVA |
| Noise level |
Oil transformer≤50db
Dry transformer≤65db |
|
| |
Related posts:
- XBZ1/XBJ1-12 Pre-installed Substation 1. General The product is made up of optimally...
- YB-12 Pre-installed Substation 1. General YB-12/0.4 pre-installed substation is used as assembly...
- What’s electrical substation? An electrical substation is a subsidiary station of an electricity...
- Electrical THE substation An electrical the substation is a subsidiary station of an...
- XGW15-12 Switching Station 1. General In large-scale intelligent switching station, the 12...
Related posts brought to you by Yet Another Related Posts Plugin.