Tellhow (Shenzhen) Electric Technologies Co., Ltd.
Chinese professional electrical equipments manufacturer

XGN15-12 Metal-enclosed Switchgear

By admin • Oct 11th, 2008 • Category: MV Metalclad and Metal-eclosed Switchgears
1. General

Applicable for single busbar distribution sub-system, AC 3ph, 3.6kV~12kV, 50/60Hz, mainly used for industrial and civil Ring Main Unit and terminal feeding station, specially suitable for sub-distribution station, switch station, the power inputting & feeding system of industrial & mining enterprise, residential block, airport, railway, tunnel, tower, etc.

Product features:

  • Cubicles made of aluminum-plated zinc sheets.
  • Metallic wire slots, arc and electromagnet proof.
  • Pressure release channel available for each compartment.
  • All operation is carried out while the door is closed.
  • Strong density of enclosure to prevent the intruding of creature or other objects, with protection
  • class IP4X.
  • Simple and effective locking design to prevent mis-operation.
  • Electric drive unit, PT, CT, UPS, FTU is adoptable.
  • Grounding switch for earthing and loop short circuit.
  • Nice outlook, well designed and compact structure.
  • Installation against the wall, maintain onsite, saving the ground.
  • Novel permanent mark and nameplate.
  • Wide application in various environment.
2. Normal Service Condition
  • Installation location: indoor
  • Ambient temperature: -15 ℃ ~ +40 ℃
  • Altitude: ≤1000m
  • Earthquake intensity ≤ 8 degree
  • If the service condition differs from the above , the user should consult it with manufacturer.
3. Cubicle Structure
Apparatus Type Manufacturer
Load break switch FLN36-12D TELLHOW
FLN38-12D TELLHOW
SFG ABB
Circuit breakers VD4 ABB
EVOLIS SCHNEIDER
HVX AREVA
TZN TELLHOW
Protection device REF ABB
SPAM SCHNEIDER
MACOM-P AREVA
TH9140 TELLHOW
Current transformers IEC ABB
LZZBJ DALIAN NO.1
LZZBJ DALIAN NO.2
Voltage transformers IEC ABB
JDZ DALIAN NO.1
JDZ DALIAN NO.2
Cabinet XGN-12 TELLHOW
4. Primary Circuit Chart
  • Busbar compartment
  • Withdrawable part compartment
  • Connections compartment
  • Relay room
5. Technical Parameters
Name Unit Parameter
Rated voltage kV 10
Max. voltage kV 12
Rated frequency Hz 50(60)
Lightning impulse withstand voltage ph-ph, ph-ground kV 75
break gap 85
1min AC
withstand voltage
ph-ph,ph-ground kV 42
break gap 48
Rated current A 630
Rated short circuit breaking current kA 20
Rated short time withstand current kA 20
Rated peak withstand current kA 50
Protection class / IP3X
Standard / IEC60420, IEC60265 ,IEC62271-200 GB3906,GB/T11022,GB3804,GB16926
Dimension (W) mm 375,500,750
(D) 1000
(H) 1635,1885

Related posts:

  1. KYN28A-12/T3150-40 Switchgear 1. General Applicable for AC 3ph, 3.6 kV~12kV, 50/60Hz...
  2. KYN28A-24/T3150-40 Switchgear 1. General Applicable for AC 3ph, 3.6 kV~24kV, 50/60Hz...
  3. KYN28A-7.2 Metalclad Switchgear 1. General KYN 28A -7.2(J.R) switchgear series adopt MV...
  4. RAG SF6 Insulated Switchgear 1. General RMU is applicable for the distribution equipment,...
  5. TKYNH-12 Metalclad Switchgear 1. General Applicable for single busbar distribution sub-system, AC...

Related posts brought to you by Yet Another Related Posts Plugin.

admin is
Email this author | All posts by admin

INQUIRY