YB-12 Pre-installed Substation

By admin • Oct 11th, 2008 • Category: Terminal Distribution Equipments
1. General

YB-12/0.4 pre-installed substation is used as assembly device for power transformation, power distribution, compensation, control and protect in power distribution system rated 10kV. Besides transformer, there’s 4-position (or 2- position) load switch, protection fuse and plug-type fuse on HV side, there is control and distribution device, compensation device and meters on the LV side. The insulation and arc extinction medium are transformer oil. It can be used in the civic buildings, virescence zone, park, station, quays, hotel, building site, airport and so on.

Product features:

  • Totally airproof, high insulation , small size, compact structure, high safety.
  • Used in ring main and terminal power supply, the cable connector can frequently plug in and out under 200A .
  • Use the overall protection with double sense fuse or stand-by fuse.
  • Corrosion-proof design., special spray-paint.
  • Low noise, high lightning protection capability.
  • Intelligent undervoltage controller installed on LV side, to ensure the safe operation of power supply.
  • Low loss, high overload capability.
  • Equipped with phase-loss protection device.
2. Normal Service Condition
  • Ambient temperature: -25 ℃ ~ + 40 ℃
  • Altitude: ≤ 2000m
  • Relative humidity: daily average relative humidity ≤ 95%; monthly average relative humidity ≤ 90%
  • Free from fire, explosion, heavy pollution, chemical corrosion and severe vibration.
  • The earthquake intensity ≤ 8 degree
  • The degrees of inclination of installation ≤3 degrees
  • If the service condition differs from the above , the user should consult it with manufacturer.
3. Structure
4. Technical Parameters
No. Item Unit Parameter
1 Rated voltage Original side kV 12
Auxiliary side 0.4
2 Rated capacity kVA 100,125,160,200,250,315,400,500,630,800
3 No-load voltage regulation - ±2╳2.5%
4 Connection method - D,yn11
5 Rated insulation level Lightning impulse withstand voltage(full wave, peak) kV 75
Power frequency withstand voltage 42
6 Power frequency withstand voltage (phase to phase, phase to ground) Main circuit 2.5
Control and measure circuit kV 2.0
7 Noise class dB ≤45
8 Protection class - IP34
9 Cooling method - ON
Load Break Switch Parameter
No. Item Unit Load switch(4-position) Load switch(2-position)
1 Lightning impulse withstand voltage(peak, full wave) Phase to ground, phase to phase kV 75 75
Breaking gap 85 85
2 Power frequency withstand voltage( 1 min) Phase to ground, phase to phase kV 42 42
Breaking gap kV 48 48
3 Rated current A 630 100
4 Rated short circuit making current(peak) kA 31.5 16
5 Rated short time withstand current kA 12.5 6.3
6 Rated peak withstand current S 2 2
7 Rated short time withstand current kA 31.5 16

Related posts:

  1. XBZ-12 Pre-installed Substation 1. General This products is a new-generation semi-embedded pre-fabricated...
  2. XBZ1/XBJ1-12 Pre-installed Substation 1. General The product is made up of optimally...
  3. RAD-12 Vacuum Circuit Breaker 1. General RAD-12/T1250-31.5 series of vacuum circuit breakers with...

Related posts brought to you by Yet Another Related Posts Plugin.